CLOSED SYSTEM TREATMENTS

Chemiteq supply a range of cleaners and inhibitors for closed systems, some of which are NSF approved (formerly BuildCert).

It is recommended that a suitable treatment programme is in place according to the Approved Code of Practice and Guidance (ACoP L8), HSG 274 and the latest BSRIA Guide.

We can also offer products which meet VDI 2035 standards. VDI theory is based on low conductivity, low dissolved oxygen and controlled pH.

All our products are tried and tested formulations. We offer a range of concentrated products which means lower dose rates, less plastic waste and a potential saving on transport. We also offer non-chemical options.

SYSTEM CLEANERS

Our system cleaners have a recommended dose rate. This is proven to work in the majority of cases. However if the system is particularly dirty, more product may be required or multiple cleans may be needed. Please see separate data sheets for further information. CQ6015 is a low dose rate product.

CQ6015 – Low dose rate

Iron & scale removal and
pre-commissioning cleaning.

Recommended dose rate =
0.25% (2.5L/m3)

pH as supplied = 7

CQ6012

Good for iron and scale removal and
pre-commission cleaning.

Recommended dose rate =
1% (10L/m3)

pH as supplied = 4-5; neutral in reaction

CQ6020

Polymer cleaner. Good for renovation of older systems. Can be used as an online cleaner. Compatible with most water treatment products.

Recommended dose rate = 1% (10L/m3)

pH as supplied = 7

SYSTEM INHIBITORS

Our inhibitors are designed to work in multimetal systems. CQ4516 and CQ4517 are for use in systems containing aluminium, whereas CQ4518 is for multimetal systems without aluminium. All our inhibitors have low dose rates.

CQ4516 – Low dose molybdate

Suitable for multi-metal systems including aluminium.
NSF certified.

Recommended dose rate: 0.25% (2.5L/m3)

pH as supplied: 7

Measurement: 100-120ppm as MoO4

CQ4518 – Low dose nitrite

Suitable for multi-metal systems without aluminium

Recommended dose rate: 0.33% (3.3L/m3)

pH as supplied: 12-13

Measurement: 800-1200ppm as NaNO2

CQ4110 – Low dose synergised nitrite

Suitable for multi-metal systems without aluminium

Recommended dose rate: 0.2% (2L/m3)

pH as supplied: 12-13

Measurement 200ppm as NaNO2

CQ4517 – Low dose molybdate/ nitrite blend

Suitable for multi-metal systems including aluminium

Recommended dose rate: 0.43% (4.3L/m3)

pH as supplied: 7

Measurement: 300ppm as MoO4 and 300ppm as NaNO2

It is highly recommended to test on both MoO4 and NaNO2
to ensure the system is functioning correctly.

CQ4518P – Low dose nitrate with pink dye

Suitable for multi-metal systems without nitrite

Recommended dose rate: 0.33% (3.3L/m3)

pH as supplied: 12-13

Measurement: 800-1200ppm as NaNO2

WATER CHEMICAL TREATMENTS

THE SCIENCE BEHIND CHEMITEQ

NON-CHEMICAL WATER TREATMENTS